What is a pneumatic pressure test?

4 min read

Asked by: Julie Roberts

Pneumatic testing is the process of using a gas to determine if a vessel can safely withstand the pressures required under normal usage. To do this, a gas is inserted and the pressure is increased above the normal pressure the vessel is designed to withstand once put in service.

What do you mean by pneumatic test?

Pneumatic Test – A pressure or tightness test where a gas, generally nitrogen or air, is the test medium. Pressure piping system – means pipes, tubes, conduits, fittings, gaskets, bolting and. other components that make up a system for the conveyance of an expansible fluid.

How is pneumatic test done?

12.1.2.3 Pneumatic test
The following two provisions are required: an adequately sized relief device and an intermediate hold at the lesser of either one-half the test pressure or 25 psi (170 kPa) with visual inspection of all joints are required prior to bringing the pressure gradually up to the full test pressure.

What is the difference between hydrostatic and pneumatic test?

There are two methods for pressure tests: hydrostatic and pneumatic. A hydrostatic test is performed by using water as the test medium, whereas a pneumatic test uses air, nitrogen, or any non-flammable and non- toxic gas. At SLAC pressure tests must be hydrostatic unless pneumatic tests can be justified.

What is the maximum pneumatic test pressure?

The pneumatic test pressure shall not be less than 1.2 nor more than 1.5 times the design pressure of the piping system. It shall not exceed the maximum allowable test pressure of any non-isolated component.

How do you perform a pressure test?

The test involves filling the vessel or pipe system with a liquid, usually water, which may be dyed to aid in visual leak detection, and pressurization of the vessel to the specified test pressure. Pressure tightness can be tested by shutting off the supply valve and observing whether there is a pressure loss.

What is the difference between leak test and pressure test?

The pressure test is usually performed at 1.1 to 1.5 times the design pressure of the system. The code leak test is applied to test the pressure boundary of the piping system and not the isolation points in the system, such as the seats or seal in valves.

What is the hazard of pneumatic testing?

The main hazard during pressure testing is the unintentional release of stored energy. In the case of pneumatic testing, this can lead to a blast wave and missiles which can be deadly.

What physical check must be performed on pneumatic equipment before the pressure is applied?

A pre-test inspection shall be made to verify proper assembly and tightness of connections, positioning of valves and all supports are installed as designed. Proper assembly, including tightness of connections, positioning of valves, over pressure protection and hangers and supports are in place as designed.

Why nitrogen is used in pneumatic test?

The reasons surrounding the use of nitrogen gas as a driver for pressure testing are due to the favorable physical and chemical properties. To begin with, nitrogen is an odorless, colorless, and chemically inert gas which implies non-reactivity with equipment components being subjected to pressure testing.

How do you test for leaks in a pneumatic circuit?

There are a number of methods used to detect leaks such as pressure decay, mass flow, bubble, sniffing and vacuum.

How do you calculate safe distance for pneumatic testing?

Safe Distance (R) = Rs(2TNT)1/3….. as per equation III-1 from ASME PCC-2 Appendix 501-III. where Rs = scaled consequence factor whose minimum value shall be 20m/kg(1/3).

Is code for pressure testing of pipe?

Two codes of major importance for pressure and leak testing are the ASME B31 Pressure Piping Code and the ASME Boiler and Pressure Vessel Code.
Test Pressures.

Code Test type
ASME B31.1 Design pressure
ASME B31.1 Lower of 100 psig or design pressure
ASME B31.1 Normal operating pressure
ASME B31.3 1.5 times design

What is the safe distance with hydro testing?

50 feet

For hydrotesting only, a minimum distance of 50 feet should be maintained between facilities that are being tested and any person, whether it be the public or the personnel conducting the test.